Hyxi Atlas HYX-EL261P2-EU
- Capacity261 kWh
- Power125 kW
- ChemistryLFP 314 Ah
- IP ratingIP55
Overview
The HYXI Atlas HYX-EL261P2-EU is a liquid-cooled energy storage system for businesses: 261 kWh and 125 kW in one outdoor cabinet, with battery, power conversion system (PCS), EMS, liquid cooling and fire protection integrated. The 314 Ah LFP cells are configured as 1P260S, with 832 V DC nominal (728 to 936 V). On the AC side the cabinet supplies 3L/N/PE 230/400 V at 180 A and 125 kW, grid-connected or in island mode with 100 percent unbalance; several cabinets can be connected in parallel.
Read the full description
Dimensions 1000 × 2402 × 1467 mm, 2620 kg, IP55 and corrosion class C5, operation from -30 to +55 °C (PCS derating from 50 °C) up to 3000 m, noise ≤ 70 dB at 1 m. Fire protection with gas detection, smoke and heat detectors, alarm sounder, smoke exhaust fan and aerosol; communication via Ethernet, Wi-Fi or 4G with Modbus TCP. Certified to IEC 62619, IEC 60730, IEC 63056, IEC 62477, IEC 61000 and UN 38.3. Hyxi provides a 5-year warranty.
Specifications
- 261 kWhCapacity
- 125 kWPower
- 2620 kgWeight
General
- Category
- Energy storage
- Product code
- 15-211
- Manufacturer code
- HYX-261 KWH
- Type
- C&I vloeistofgekoelde ESS
- Series
- Atlas
- Model
- HYX-EL261P2-EU
- Segment
- Commercieel
Power and efficiency
- Capacity
- 261 kWh
- Power
- 125 kW
- Chemistry
- LFP 314 Ah
Electrical
- Communication
- Ethernet, Wi-Fi, 4G (Modbus TCP)
- Nominal voltage
- 832 V (728-936 V)
Mechanical
- Dimensions
- 1000 × 2402 × 1467 mm
- Weight
- 2620 kg
- IP rating
- IP55
Warranty
- Warranty
- 5 jaar
Other
- Energie
- 261 kWh
- Koeling
- Vloeistof
- Corrosieklasse
- C5
- Celconfiguratie
- 1P260S
From carton to a working system
Official HYXiPOWER installation video for the HYX-EL261P2-EU range. The footage covers this product family, not only this article.
Source: HYXiPOWER, official product family.
Questions
The short ones are here. For anything else, ask below.
The HYXI Atlas HYX-EL261P2-EU is a liquid-cooled energy storage system for businesses: 261 kWh and 125 kW in one outdoor cabinet, with battery, power conversion system (PCS), EMS, liquid cooling and fire protection integrated. The 314 Ah LFP cells are configured as 1P260S, with 832 V DC nominal (728 to 936 V). On the AC side the cabinet supplies 3L/N/PE 230/400 V at 180 A and 125 kW, grid-connected or in island mode with 100 percent unbalance; several cabinets can be connected in parallel.
Hyxi Atlas HYX-EL261P2-EU is rated 125 kW.