KSTAR BluePulse BC107DE2 CATL
Product code 06-111Manufacturer code 1035G0045
- 107,52 kWhCapacity
- 6000 (80% EOL) / 8000 (70% EOL)Cycles
- 90% (recommended)DoD
Overview
The KSTAR BC107DE2 is the 107.52 kWh outdoor battery cabinet of the BluePulse series, in an enclosure of 1062 × 2083 × 1371 mm. Six 17.92 kWh LFP modules with 280 Ah cells form one 384 V cluster (operating range 342–432 V). Charging and discharging run at up to 0.5C with a rated current of 140 A; actual power is limited by the connected PCS. Its own BMS and EMS unit control the cabinet, an air conditioner cools or heats, and fire safety comes from carbon monoxide detection, a sound and light alarm, an exhaust fan, an explosion vent and a fire-water inlet. At about 1430 kg, IP54 and corrosion class C4 it is installed outdoors at -30 to +50 °C. Communication via Ethernet, CAN and RS485. KSTAR pairs the BC107DE2 with a PCS from the KAC50DP2 or KAC80-125DP2 series.
Specifications
General
- Product code
- 06-111
- Manufacturer code
- 1035G0045
- Type
- Outdoor C&I battery cabinet (LFP) with EMS unit
- Series
- BluePulse
- Model
- BC107DE2
- Segment
- Commercial
Power and efficiency
- Capacity
- 107,52 kWh
- Charge power
- 0,5C (140 A), limited by the PCS
- Chemistry
- LFP
- Cell type
- LFP 280 Ah
- Cycles
- 6000 (80% EOL) / 800070% EOL
- DoD
- 90%recommended
Electrical
- Communication
- Ethernet / CAN / RS485Modbus TCP/IP
Mechanical
- Dimensions
- 1062 × 2083 × 1371 mm
- Weight
- ca. 1430 kg
- IP rating
- IP54
Warranty
- Warranty
- 5 years product / 10 years performance70% usable energy
Questions
The short ones are here. For anything else, ask below.
The KSTAR BC107DE2 is the 107.52 kWh outdoor battery cabinet of the BluePulse series, in an enclosure of 1062 × 2083 × 1371 mm. Six 17.92 kWh LFP modules with 280 Ah cells form one 384 V cluster (operating range 342–432 V). Charging and discharging run at up to 0.5C with a rated current of 140 A; actual power is limited by the connected PCS. Its own BMS and EMS unit control the cabinet, an air conditioner cools or heats, and fire safety comes from carbon monoxide detection, a sound and light alarm, an exhaust fan, an explosion vent and a fire-water inlet. At about 1430 kg, IP54 and corrosion class C4 it is installed outdoors at -30 to +50 °C. Communication via Ethernet, CAN and RS485. KSTAR pairs the BC107DE2 with a PCS from the KAC50DP2 or KAC80-125DP2 series.
KSTAR BluePulse BC107DE2 CATL is 107,52 kWh.